The 14kW, 16kW and 18kW models list off-grid peak power of 28kVA, 32kVA and 36kVA. This gives short-duration reserve for pumps, compressors and other loads that draw high current when starting. The 3 phase inverter should still be selected from the normal continuous load first, then checked against motor inrush and the duration of the startup event. Peak capacity cannot be used as the continuous operating target, and simultaneous motor starts may require additional headroom.